3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
The facilities were not maintained in a safe, clean & sanitary, and in good repair. Chlorine pump is leaking.
REPAIR LEAK FROM THE CHLORINE PUMP Correct By: 21-Jun-2023
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches. One place it was 8 inches between the bottom of the fence and the ground.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
MODIFY THE FENCE TO ELIMINATE THE GAP UNDER THE FENCE.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FUNCTION MONTHLY. Correct By: 27-Jun-2023
3701-31-04 (E)(2)(b)(i) / 12 ft. non-telescopic reach pole with Sheppard's crook & a USCG Type IV personal flotation device with 30 - 60 foot throw line.
Personal flotation device with 30 - 60 foot throw line was not provided at the guarded pool.
Provide a Personal floatation device at the pool at all times.
PLACE THE RING BUOY IN THE POOL AREA. Correct By: 21-Jun-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-June-2023
Comments |
---|
The Certificate of Compliance is not available for the main drain cover. Keep a copy at the facility for future review. Keep documentation of the ASSE 1013 backflow preventer’s annual inspection available at the pool facility for review by the health department. LIFEGUARD MUST KEEP A CPR MASK WITH THEM WHEN ON DUTY. |