3701-31-04 (B) / All facilities are maintained clean, safe and sanitary condition and in good repair.
Concrete at pool entrance and holes where ladder has been removed is damaged.
Repair damaged concrete to provide a hazard free surface. Correct By: 29-Jul-2014
3701-31-04 (B)(5) / Records are maintained for at least two years
Records were not maintained for at least two years.
Maintain all records and have them available upon request. Correct By: 22-Jul-2014
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
Flowmeter not working. Repair or replace flowmeter so that turnover rate can be monitored.. Correct By: 22-Jul-2014
3701-31-04 (E)(2)(a)(ii) / A USCG Type IV personal flotation device with 30 -60 foot throw line provided
A USCG Type IV personal flotation device with 30 -60 foot throw line was not provided at the unguarded pool.
Provide 30-60 foot throw line on flotation device. Correct By: 16-Jul-2014
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
A back/spine board without a head immobilizer and straps was not provided at the unguarded pool.
Provide the back/spine board at the pool at all times. Correct By: 16-Jul-2014
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 14-June-2014