3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
CONTACT THE OHIO DEPARTMENT OF HEALTH FOR APPROVAL OF THE FENCE.
REPORTEDLY, THE PROPERTY MANAGEMENT COMPANY IS IN THE PROCESS OF CONTACTING ODH. Correct By: 15-Jun-2021
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FLOW RATE TO AT LEAST 56 GPM. Correct By: 15-Jun-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY. ADDING 7 LBS. OF BAKING SODA ( SODIUM BICARBONATE) SHOULD RAISE THE ALKALINITY TO 100 PPM. Correct By: 15-Jun-2021
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 29-June-2021