[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Flow rate exceeds the maximum allowable flow for the filter.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO 48 GPM OR LESS. Correct By: 30-Jul-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Test ACC unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST AND RECORD ACC FLOW SWITCH RESULTS ON THE WEEKLY LOG SHEET. Correct By: 30-Jul-2022


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 28-July-2022

Comments
DATE MARK THE WEEKLY LOG SHEETS.

KEEP THE CHEMICAL SDS (SAFETY DATA SHEETS) IN THE EQUIPMENT ROOM. HAVE AVAILABLE AND USE THE PPE (PERSONAL PROTECTIVE EQUIPMENT SUCH AS CHEMICAL GLOVES AND GOGGLES).