3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat The drain covers were installed at an unknown date.
IF THE DRAIN COVERS ARE MORE THAN 5 YRS OLD OR IF THE DATE OF INSTALLATION IS UNKNOWN REPLACE THE COVERS. Correct By: 15-May-2019
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is .4 which is level than required.
The violation is a critical operational item and poses an imminent health hazard.
THE POOL MUST CLOSE IMMEDIATELY AND MUST REMAIN CLOSED UNTIL THE FREE CHLORINE LEVEL IS AT LEAST 1 PPM. Correct By: 24-Jul-2018
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps have an air gap and are open to freely drain
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
INSTALL AN IAR GAP ON THE FILTER BACK WASH LINE. Correct By: 01-Aug-2018
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE THE FOW RATE TO AT LEAST 84 GPM BUT LESS THAN 98 GPM
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 25-July-2018