3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR/REPLACE PRESSURE GAUGE ON THE FILTER. Correct By: 23-Jun-2021
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HANDRAIL TO THE STEPS. Correct By: 17-Jun-2021
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH. Correct By: 17-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-June-2021
Comments |
---|
The operator was observed performing onsite chemical tests appropriately The Certificate of Compliance for the main drain cover is available in the office. Our records show that the main drain suction outlet covers (Hayward WG1048E) were installed 5/15/2018. The covers have a 7 year life span and must be replaced before 5/15/2025. Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm |