3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is 0.
AT LEAST 1 PPM FREE CHLORINE IS REQUIRED. INCREASE AND MAINTAIN FREE CHLORINE LEVEL AT 1 PPM OR MORE. THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. THE POOL MUST IMMEDIATELY CLOSE UNTIL THE VIOLATION IS CORRECTED AND THE HEALTH DEPARTMENT VERIFIES COMPLIANCE. CALL THE HEALTH DEPARTMENT WHEN THE CORRECTION HAS BEEN MADE AT 440-322-6367. Correct By: 22-Aug-2017
3701-31-04 (B)(1)(k) / Chemical storage or use shall not result in imminent health hazard.
Critical Repeat Corrected During Inspection Different type chemicals were stacked on top of each other. Ant poison was stacked on top of Calcium Plus in the filter room.
TO AVOID CHEMICAL HAZARD, STORE DIFFERENT CHEMICALS SEPARATELY AND NOT ON TOP OF EACH OTHER. Correct By: 25-May-2017
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
The rubber coupling is used to joint two lengthens of pipe.
REPLACE THE RUBBER COUPLING WITH SOLID APPROVED PIPE. Correct By: 25-Jun-2017
3701-31-04 (B)(6)(c)(v) / Discharge of water from a public swimming pool shall be in accordance with OEPA.
The backwash drain to the sewer does not have a proper air gap.
INSTALL AN AIR GAP ON THE BACKWASH DISCHARGE LINE. REPEAT VIOLATION. Correct By: 26-May-2017
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical The filter room was not locked.
TO KEEP CHEMICALS INACCESSIBLE, KEEP THE FILTER ROOM LOCKED. Correct By: 25-May-2017
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 22-August-2017