3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is .4 ppm.
This is a critical operational item and poses an imminent health hazard.
CLOSE THE SPA UNTIL AT LEAST 2 PPM FREE CHLORINE CAN BE MAINTAINED. RAISE THE FREE CHLORINE LEVEL TO AT LEAST 2 PPM. CALL THE HEALTH DEPARTMENT WHEN THE VIOLATIONS ARE CORRECTED. Correct By: 07-Nov-2019
3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Repeat Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
This violation is a critical operational item and poses an imminent health hazard.
THE SPA MUST CLOSE UNTIL THE AUTOMATIC CHEMICAL CONTROLLER IS REPAIRED. CALL THE HEALTH DEPARTMENT WHEN THE ACC IS REPAIRED. Correct By: 07-Nov-2019
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 07-Nov-2019
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
Repeat A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
THE PUMP CURVE AND THE CALCULATIONS FOR DETERMINING THE FLOW RATE WERE NOT POSTED. POST BOTH IN THE PUMP ROOM. BOTH ARE BEING SUPPLIED TO THE OPERATOR FOR THE SECOND TIME. Correct By: 07-Nov-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 07-November-2019