3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Repeat Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPLACE THE FLOW METER. THE LOCATION OF THE FLOW METER MUST MEET THE MANUFACTURER'S DIRECTIONS. Correct By: 14-Jul-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Fence with not around the wading pool.
INSTALL FENCE AROUND THE WADING POOL. OBTAIN PLAN APPROVAL FROM THE OHIO DEPARTMENT OF HEALTH. Correct By: 31-Aug-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-July-2020
Comments |
---|
-Wading pool volume was recalculated using 7 inch depth at the perimeter of the pool and 15 inches at the middle of the pool. This is when the water is at the middle of the skimmer opening. -Keep the chemicals’ Safety Data Sheets (MSDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. -The Certificate of Compliance was not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. -Our records show that the main drain suction outlet cover (AquaStar WAV 12) was installed 5/1/2016. The cover has a 5 year life span and must be replaced before 5/1/2021. |