3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE DISINFECTION CHEMICAL FEEDER PUMP CHANGE. THE STENNER 100DM5 WAS REPLACED WITH A STENNER 85M5. Correct By: 23-Mar-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired.
INCREASE FLOW RATE TO AT LEAST 331 GPM. Correct By: 23-Mar-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 20-March-2023
Comments |
---|
The Certificate of Compliance is not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet covers (Lawson MLD-FGD-1818) were installed 3/13/2020. The covers have a 10 year life span and must be replaced before 3/13/2030. Maximum flow rating is 816 gpm The operator (lifeguard) was given tips on water testing to improve the accuracy of the results. THE SKIMMER LOCATED CLOSEST TO THE GUARD OFFICE IS NOT DRAWING WATER. THE SKIMMER SHOULD BE REPAIRED IF POSSIBLE. |