3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. A hose is attached to the pool circulation system without a backflow preventer.
Remove all cross connection hazards from the pool area.
INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB IN THE FILTER ROOM. A BACKFLOW PREVENTER LIKE THE ONE BY THE SPA IS ACCEPTABLE. Correct By: 11-Feb-2018
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices are maintained
Backflow prevention device (ASSE 1013) was not inspected within 12 months.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
HAVE THE BACKFLOW PREVENTER ASSE 1013 INSPECTED AND TAGGED AS INSPECTED. Correct By: 11-Feb-2018
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The "NO DIVING" sign was missing by the ADA chair.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
INSTALL THE "NO DIVING" SIGN BY THE ADA LEFT CHAIR. Correct By: 11-Feb-2018
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents. The acid tank is not labeled and the chlorine tank label cannot be seen.
The pH adjusting chemicals are stacked on top of each other.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
LABEL THE ACID AND CHLORINE TANKS SO THEY CAN BE PLAINLY SEEN. Correct By: 12-Jan-2018 Correct By: 12-Jan-2018
MOVE THE CHEMICALS (pH ADJUSTING CHEMICALS) FROM ON TOP OF EACH OTHER. DO NOT STACK DIFFERENT TYPES OF CHEMICALS ON EACH OTHER. Correct By: 12-Jan-2018 Correct By: 12-Jan-2018 Correct By: 12-Jan-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm. Alkalinity was 50 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE THE ALKALINITY LEVEL TO 60 PPM OR MORE. Correct By: 12-Jan-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-January-2018
Comments |
---|
TIGHTEN THE HANDRAIL AT THE STEPS IF POSSIBLE. IF THE FIRST AID KIT IS KEPT AT THE FRONT DESK, POST A SIGN IN THE POOL AREA INDICATING ITS LOCATION. |