[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day. RECORD TEMP DAILY Correct By: 27-Jul-2019
3701-31-04 (B)(6)(bb)(vi) / Diving board fulcrums fixed or adjustable shall be locked in the forward most position.
Diving board fulcrums were not fixed or locked in the forward most position during noncompetition use.
Ensure that the fulcrum is either fixed or locked in the forward most position during noncompetition events. MOVE THE DIVING BOARD FULCRUM TO THE FORWARD MOST POSITION Correct By: 01-Aug-2019
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO BETWEEN 635 AND 1328 GPM
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. RECORD MONTHLY ACC FLOW SWITCH FUNCTION Correct By: 27-Jul-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 25-July-2019