3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT OF THE DISINFECTION UNIT. FLEX FLO A1N10A-7T WAS REPLACED WITH A FLEX FLO A1N30A-T7. Correct By: 24-Jun-2020
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely.
PROVIDE AN AIR GAP ON THE FILTER DISCHARGE LINE. Correct By: 24-Jun-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 24-Jun-2020
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
REPAINT THE DEPTH MARKING AND NO DIVING SIGNS Correct By: 24-Jun-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemicals not stored properly.
INCREASE THE VENTILATION IN THE EQUIPMENT ROOM TO REDUCE THE ROOM TEMPERATURE. Correct By: 24-Jun-2020
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
STORE THE TEST KIT IN ROOM AT 85 DEGREES OR LESS.
Correct By: 19-Jun-2020
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 19-June-2020
Comments |
---|
OKAY TO OPEN POOL. A REINSPECTION WILL BE MADE TO VERIFY COMPLIANCE WITH ALL OTHER VIOLATIONS. |