[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The skimmer is missing a weir.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate exceeds the maximum allowable flow of the filter.of 50 gpm
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO 50 GPM OR LESS. Correct By: 10-May-2019
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant. The bottom step on the ladder is missing the tread.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. REPLACE THE MISSING TREAD ON THE BOTTOM STEP ON THE LADDER.
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Repeat Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure. LABEL THE CHLORINE TANK.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH Correct By: 10-May-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 08-May-2019

Comments
ALL 4 SCREWS MUST BE USED IN THE MAIN DRAIN COVER
THE RUBBER COUPLING ON THE PIPE IN THE FILTER ROOM MUST BE REPLACED WITH A RIGID PVC PIPE MEETING ASTM F44/F441M-99 OR EQUIVALENT
THE HOSE BIB SHOULD NOT BE ON THE WATER LINE THAT IS DIRECTLY CONNECTED TO THE POOL AFTER THE BACKFLOW PREVENTER