3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. The flow meter is installed improperly. 8" downstream from a 90 degree pipe turn.
All equipment must be maintained in accordance with the manufacturers specifications.
RELOCATE THE FLOW METER AT LEAST 20 INCHES DOWNSTREAM FROM THE ELBOW ON THE 2 INCH DIAMETER PIPE AND AT LEAST 10 INCHES UPSTREAM FROM THE ELBOW. Correct By: 05-Jul-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 05-June-2017
Comments |
---|
PLEASE ADD THE WORD "WARMING" TO THE nO LIFEGUARD SIGN |