3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
KEEP POOL CLOSED UNTIL FREE CHLORINE LEVEL IS AT 1 PPM OR HIGHER.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Perimeter barrier had gaps greater than 4 inches.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
ELIMINATE THE LARGE GAP UNDER THE FENCE BY THE GAZEBO. GAP MUST BE LESS THAN 4 INCHES.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH
3701-31-04 (D)(05) / Cyanuric acid level shall not exceed 70 ppm.
Cyanuric acid level exceeded 70 ppm
Drain the pool at least halfway and fill with clean water. Monitor the amount of cyanuric acid being used and adjust accordingly.
DRAIN POOL PARTIALLY AND REFILL TO REDUCE CYA.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 19-July-2022
Comments |
---|
POOL WAS NOT OPEN AT THE TIME OF INSPECTION |