3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is 0 ppm.
This violation is a imminent health hazard. CLOSE THE POOL UNTIL THE FREE CHLORINE LEVEL IS 1 PPM OR MORE. PLEASE CALL THE HEALTH DEPARTMENT WHEN THE VIOLATION HAS BEEN CORRECTED. Correct By: 04-Dec-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The UV light is not working.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE UV LIGHT.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present. The hose bib under the eye wash station is not backflow protected.
Remove all cross connection hazards from the pool area.
INSTALL AN ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB THAT IS LOCATED UNDER THE EYE WASH STATION.
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 04-December-2018