3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 958 GPM. Correct By: 22-Jul-2022
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPLACE PRESSURE GAUGE ON THE FILTERS
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 20-July-2022