[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results records were not maintained.
The test results/service records for these devices must be kept on site for review. TEST AND RECORD THE PRESSURE SWITCH FUNCTION ON THE ACC MONTHLY. Correct By: 04-Apr-2024
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
Obtain fresh reagents and store them properly. REPLACE THE EXPIRED ALK REAGENTS IN THE TEST KIT. Correct By: 04-Apr-2024


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 28-February-2024

Comments
Documentation of the ASSE 1013 backflow preventer’s annual inspection is available at the pool facility for review.

The Certificate of Compliance for the main drain covers is available in the equipment room.

Our records show that the main drain suction outlet covers (Waterway 642-3630v SPC-3) were installed on 9/11/2019. The covers have a 7 year life span and must be replaced before 9/11/2026.

The operator was observed performing onsite chemical tests appropriately and is aware of the acceptable parameters and necessary corrective actions.