[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation. REPAIR THE FLOW SWITCH ON THE AUTOMATIC CHEMICAL CONTROLLER. Correct By: 12-Aug-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Corrected During Inspection The door/gate to the pool was left open.
KEEP THE FRONT DOOR/GATE CLOSED Correct By: 10-Aug-2019
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 12-Aug-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-August-2019

Comments
It is not a good practice to store hay bails in the chemicals storage room.

A proper ring buoy was provided