3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 100 GPM Correct By: 15-Feb-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
INCREASE pH. Correct By: 15-Feb-2022
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 08-February-2022
Comments |
---|
I COULD NOT DETERMINE IF THE UV LIGHT WAS FUNCTIONING PROPERLY. |