[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated. PLACE AT LEAST 2 DEPTH MARKINGS AT THE ZERO ENTRY THAT READ "ZERO DEPTH"OR "O FT"OR "0 IN"
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. RECORD ACC FUNCTION ON THE WEEKLY OPERATIONAL SHEET


Inspection Information


Facility Type: Special Use

[?] Inspection Type: Standard

Inspection Date: 25-July-2019

Comments
Corrections made since the 6-28-19 inspection
-Pump is operating properly
-skimmers have baskets and weirs
-chlorine tank is labeled