3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Repeat Depth markers/deck warning signs were not maintained in a clearly legible/visible manner.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE AT LEAST 2 DEPTH MARKINGS AT THE ZERO ENTRY THAT READ "ZERO DEPTH"OR "O FT"OR "0 IN"
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
RECORD ACC FUNCTION ON THE WEEKLY OPERATIONAL SHEET
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 25-July-2019
Comments |
---|
Corrections made since the 6-28-19 inspection -Pump is operating properly -skimmers have baskets and weirs -chlorine tank is labeled |