3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
The licensee /authorized representative was not keeping or maintaining operational records. Pool testing was not done daily.
All facility records must be maintained and available for review upon request.
TEST AND RECORD POOL READINGS DAILY EVERY 12 HOURS. TEST AND RECORD THE ACC FUNCTION MONTHLY. Correct By: 18-Aug-2020
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Some reagents have expired.
REPLACE EXPIRED REAGENTS. PLAN TO REPLACE THE KIT ANNUALLY. Correct By: 18-Aug-2020
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
RESTOCK FIRST AID KIT. Correct By: 18-Aug-2020
3701-31-04(D)(6)(a)(1) / Combined chlorine shall not exceed 1.0 ppm.
Combined chlorine was greater than 1.0 ppm.
Treat the pool so that the combined chlorine is less than 1 ppm.
SUPER CHLORINATE THE POOL AND INCREASE VENTILATION WHILE DOING SO TO DECREASE COMBINE CHLORINE. Correct By: 18-Aug-2020
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-August-2020