3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
AFTER ADJUSTING THE CHLORINE LEVEL ADJUST THE pH Correct By: 28-Jan-2022
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH Correct By: 28-Jan-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 28-Jan-2022
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
AFTER ADJUSTING THE CHLORINE ADJUST THE ALKALINITY. Correct By: 28-Jan-2022
3701-31-04 (D)(7) / Public spa shall have a functional automatic chemical controller
Critical The automatic chemical controller for the spa was not functioning properly. ORP was reading 775. Chlorine level was well over 20 ppm and the pH level was above 8.0.
THIS IS A CRITICAL OPERATIONAL ITEM AND POSES AN IMMINENT HEALTH HAZARD. CLOSE THE SPA UNTIL THE ACC IS REPAIRED AND THE LEVELS RETURN TO ACCEPTABLE LEVELS.
REPAIR AUTOMATIC CHEMICAL CONTROLLER. Correct By: 28-Jan-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC MONTHLY. Correct By: 28-Jan-2022
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 26-January-2022
Comments |
---|
Free Chlorine was over 20 ppm (outside of the range of the testing kit). COMPLETELY EMPTY THE SPA EVERY 30 DAYS AND RECORD THIS ON THE RECORD SHEET. |