3701-31-04 (B)(6)(bb)(vi) / Diving board fulcrums fixed or adjustable shall be locked in the forward most position.
Repeat Diving board fulcrums were not fixed or locked in the forward most position during noncompetitive use.
Ensure that the fulcrum is either fixed or locked in the forward most position during noncompetitive events.
MOVE THE DIVING BOARD FULCRUM TO THE FORWARD MOST POSITION.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO BETWEEN 635 AND 1328 GPM
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
RECORD ACC FUNCTION TEST RESULTS ON OPERATIONAL SHEET
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 16-August-2019