3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Equipment, at a public swimming pool, was changed/altered without obtaining approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN).
Obtain approval from the Ohio Department of Health (ODH) by submitting an Equipment Replacement Notification (ERN) before operating pool.
SUBMIT AN ERN FOR THE REPLACEMENT OF THE CIRCULATION PUMP. Correct By: 15-Jun-2022
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. Flow rate exceeds max filter flow rate.
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE FLOW RATE TO 49 GPM OR LESS. Correct By: 10-Jun-2022
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 08-June-2022
Comments |
---|
The Certificate of Compliance for the main drain cover(s) is/are available in the lifeguard room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed on 5-14-19. The covers have a 7 year life span and must be replaced before 5/14/2026. |