[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records.
All facility records must be maintained and available for review upon request. TEST AND RECORD THE FREE, COMBINE AND TOTAL CHLORINE, AND pH EVERY 4 HRS, WATER TEMPERATURE DAILY, ALKALINITY AND CYANURIC ACID WEEKLY, AND TEST THE SVRS MONTHLY Correct By: 20-Jul-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The max filter flow of 63 gpm was exceeded.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW TO 63 GPM OR LESS. Correct By: 26-Jul-2018
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Replacement pipe was not rigid PVC or equivalent. Rubber couplings were used to attach piping.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools. REPLACE THE RUBBER COUPLING WITH RIGID PIPE. Correct By: 15-May-2019
3701-31-04 (B)(6)(c)(ii) / Backwash lines and lines from drainage sumps shall have an air gap and remain open to freely drain.
Backwash lines and lines from drainage sumps did not have an air gap prior to discharge
Open the lines that discharge into the backwash or drainage sumps so that there is an air gap and the lines can drain freely. INSTALL AN AIR GAP ON THE BACKWASH DISCHARGE LINE FROM THE FILTERS. Correct By: 15-May-2019
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not tagged with the maximum minimum flow rates.
PLACE THE MAXIMUM ALLOWABLE FLOW RATE (63 GPM) AND THE MINIMUM REQUIRED FLOW RATE (37 GPM) ON THE PIPE BY THE FLOW METER. Correct By: 26-Jul-2018
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant. The ladder was loose.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair. TIGHTEN THE LADDER. Correct By: 26-Jul-2018
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate latch is broken.
REPLACE THE BROKEN LATCH ON THE GATE. Correct By: 26-Jul-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 20-Jul-2018
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. Correct By: 20-Jul-2018
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Repeat A test kit was not able to test combine or total chlorine, cyanuric acid.
OBTAIN A TEST KIT THAT CAN TEST FREE, COMBINE, AND TOTAL CHLORINE, ALKALINITY, pH, AND CYANURIC ACID. OBTAIN A THERMOMETER. Correct By: 26-Jul-2018
3701-31-04 (E)(2)(a)(iii) / A back/spine board is provided
A back/spine board without a head immobilizer and straps was not provided at the unguarded pool.
Provide the back/spine board at the pool at all times. KEEP THE SPINE BOARD OUT ON THE POOL DECK AREA WHEN THE POOL IS OPEN. Correct By: 20-Jul-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 19-July-2018

Comments
I WILL CHECK TO SEE IF THE BACKFLOW ON THE FILL LINE IS ACCEPTABLE.