3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
SVRS/APSOS/ACC test results/ service records were not maintained.
The test results/service records for these devices must be kept on site for review. If the device has not been recently serviced, have the device tested immediately and provide documentation of the test results.
TEST AND RECORD THE SVRS AND THE ACC FUNCTION ON THE LOG SHEET. Correct By: 24-Mar-2021
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE SKIMMER SO IT DRAWS AT LEAST 50% OF THE WATER TO THE FILTERS. Correct By: 30-Mar-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
INCREASE ALKALINITY. Correct By: 24-Mar-2021
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
INSTALL A FLOW SWITCH OR PRESSURE SWITCH FOR THE SPA AUTOMATIC CHEMICAL CONTROLLER. Correct By: 23-Apr-2021
Facility Type: Spa
[?] Inspection Type: Standard
Inspection Date: 23-March-2021
Comments |
---|
The main drain suction outlet cover (New Water Solutions DS 360) was installed on 10/26/2018 . The cover has a 5 life span and must be replaced before 10/26/2023. YOU CAN INCREASE ALKALINITY FOR THE SPA BY ADDING BAKING SODA (sodium bicarbonate). ABOUT .9 LBS SHOULD RAISE THE ALKALINITY TO A MORE ACCEPTABLE LEVEL THE MURIATIC ACID SHOULD THEN LOWER THE pH IF THE AUTOMATIC CHEMICAL CONTROLLER IS WORKING PROPERLY. CHECK THE SKIMMER AS IT DOES NOT SEEM TO BE DRAWING ANY WATER. AT LEAST 50% OF THE WATER SHOULD BE DRAWN THROUGH THE SKIMMERS DURING CIRCULATION AND FILTRATION. |