3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
TEST WATER TEMP DAILY AND RECORD ON THE LOG SHEET Correct By: 12-Jun-2021
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
TEST ALKALINITY WEEKLY AND RECORD ON LOG SHEET. Correct By: 12-Jun-2021
3701-31-04 (B)(6)(aa) / The Diving area/components are in good repair. No alterations have been made without plan approval
The diving board was not in good repair. End of one board is slippery.
Repair the diving board or replace the diving board with one of equal length and structure.
REAPPLY NON-SLIP SURFACE ON THE DIVING BOARD THAT IS MISSING A SLIP RESISTANT SURFACE. Correct By: 14-Jun-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 12-Jun-2021
3701-31-04 (B)(6)(p) / Deck surfaces are free of standing water or other hazards.
Deck surfaces had standing water or other hazards. Tile missing at the pool edge.
Repair areas of the deck where standing water is occurring.
REATTACH MISSING TILE FROM THE POOL EDGE. Correct By: 14-Jun-2021
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
The test kit provided was not in good repair. Reagents expired.
Maintain the test kit in good repair to conduct water quality tests.
REPLACE EXPIRED REAGENTS. Correct By: 12-Jun-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 11-June-2021
Comments |
---|
The Certificate of Compliance is not available for the main drain cover. One was supplied to operator at the time of inspection. Keep a copy at the facility for future review. Our records show that the main drain suction outlet covers (AquaStar P18) were installed 9/10/2018. The covers have a 5 year life span and must be replaced before 9/10/2023. THE MINIMUM REQUIRED FLOW RATE IS 635 GPM. PLANS SHOULD BE MADE TO REPAIR OR REPLACE THE PUMP WITH ONE THAT WILL MAINTAIN THE REQUIRED FLOW RATE. LOCK EQUIPMENT ROOM WHEN POOL IS IN OPERATION. PROVIDE IN POOL AREA THE RING BUOY AND REACH POLE WITH SHEPHERD'S CROOK WHEN IN OPERATION. WATER ADDED AT TIME F INSPECTION TO BRING LEVEL SLIGHTLY ABOVE THE GUTTER LEVEL. SMALL DECK AREA HAS PEELING PAINT WHICH COULD BE HAZARDOUS TO BARE FEET. REPAIRS NEEDED AT SOME POINT. |