3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The equalizer suction outlets are not covered with VGB compliant covers.
INSTALL VGB COMPLIANT COVERS OVER THE EQUALIZER OUTLETS OR PLUG THE OUTLET AT THE POOL WALL. Correct By: 16-Jun-2017
3701-31-04 (B)(6)(c)(i) / Backflow prevention devices shall be maintained.
Backflow prevention devices were not maintained to function properly. The ASSE 1011 backflow preventer was removed from the hose bib in the filter shed.
Have the backflow prevention device evaluated or replaced so that backflow is prevented.
REINSTALL THE ASSE 1011 BACKFLOW PREVENTER ON THE HOSE BIB IN THE FILTER ROOM. Correct By: 16-Jun-2017
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps. The flow meter is improperly located on the pipe. It is only 11 inches downstream from the elbow on a 2 inch pipe.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
INSTALL THE FLOW METER AT LEAST 10 TIME THE DIAMETER OF THE PIPE DOWNSTREAM FROM A TURBULENCE AND AT LEAST 5 TIMES THE DIAMETER OF THE PIPE UPSTREAM FROM TURBULENCE. Correct By: 09-Jul-2017
3701-31-04 (B)(6)(q) / Depth markers/deck warning signs are maintained
Depth markers/deck warning signs were not maintained in a clearly legible/visible manner. The "No Diving" markings are more than 25 ft apart.
Replace the depth markers/deck warning signs so that bathers are able to clearly see the depth of the water and that no diving is permitted where clearly indicated.
PLACE ADDITIONAL "NO DIVING" SIGNS ON THE DECK SO THEY ARE NO MORE THAN 25 FT APART. Correct By: 09-Jul-2017
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Several of the reagents are expired.
OBTAIN FRESH REAGENTS AND REPLACE BEFORE THEY EXPIRE. Correct By: 16-Jun-2017
3701-31-04 (E)(3)(b) / "Children must be supervised" or "Swimming alone is not recommended" signs posted
The unguarded pool was in use without the "Children must be supervised" and/or "Swimming alone is not recommended" signs posted.
Post the "Children must be supervised" and/or "Swimming Alone is Not Recommended" signs at all times the pool is available for use.
POST "SWIMMING ALONE IS NOT RECOMMENDED" SIGN. Correct By: 16-Jun-2017
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 09-June-2017