[?] A summary of the violations found during the inspection are listed below.

3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO AT LEAST 76 GPM.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 09-August-2022

Comments
Correction made since the last inspection dated 7-11-22
-an ASSE 1013 backflow preventer is in place.
-All necessary depth markings are in place.
-ring buoy with rope is in the pool area

CDC DOES NOT RECOMMEND CHLORINE LEVELS TO EXCEED 10 PPM