3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. The flow rate through the filters is 42 gpm which is higher that the filter max allowable flow of 38 gpm
All equipment must be maintained in accordance with the manufacturers specifications.
REDUCE THE FLOW RATE TO BETWEEN 31 AND 38 GPM. Correct By: 20-Jul-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
Repeat pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH TO BETWEEN 7.2 AND 7.8. Correct By: 12-Jul-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 10-July-2018
Comments |
---|
Our records show that new New Water Solutions DS 360 drain covers were installed 6-5-18. The covers have a life span of 5 years and must be replaced before 6-5-23. |