[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Cross connection hazards were present. The hose bibs and not backflow protected.
Remove all cross connection hazards from the pool area. PLACE ASSE 1011 BACKFLOW PROTECTORS ON ALL HOSE BIBS. Correct By: 02-Aug-2019
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation. REPAIR FLOW METER Correct By: 04-Jul-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
There are places along the fence where the gap between the bottom of the fence and the ground is more than 4 inches.
FIX THE FENCE SO THERE ARE NO GAPS GREATER THAN 4 INCHES BETWEEN THE BOTTOM OF THE FENCE AND THE GROUND. Correct By: 02-Aug-2019
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate does not self-close and latch.
INSTALL A SPRING ON THE GATE SO THAT IT SELF-CLOSES AND LATCHES. Correct By: 02-Aug-2019
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly. TEST ACC FLOW SWITCH MONTHLY AND RECORD. Correct By: 04-Jul-2019
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR EMERGENCY PHONE. Correct By: 04-Jul-2019


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 02-July-2019

Comments
Our records show: The main drain suction outlet cover (Waterway 640-472xV) was installed 5/1/2016. The cover has a 7 year life span and must be replaced before 5/1/2023.