3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. Correct By: 21-Sep-2018
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Repeat Flow or pressure switch for a shut off valve was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD ACC FUNCTION MONTHLY. Correct By: 21-Sep-2018
3701-31-04 (E)(2)(a)(i) / 12 ft. non-telescopic reach pole with shepherd's crook is provided
Repeat 12 ft. non-telescopic reach pole with shepherd's crook was not provided.
Provide a 12 ft. non-telescopic reach pole in the pool area at all times.
MAKE THE POLE 12 FT AND NON-ADJUSTABLE. Correct By: 21-Sep-2018
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 19-September-2018