3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level was 0 ppm.
INCREASE THE FREE CHLORINE LEVEL TO AT LEAST 1 PPM. THE POOL MUST NOT BE OPEN FOR SWIMMERS UNTIL THE LEVEL REACHES ACCEPTABLE LEVEL. Correct By: 19-Jul-2018
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 19-July-2018
Comments |
---|
Our records show that the main drain covers (Hayward WG1048E) were replaced on 5-15-2018. The covers have a life span of 7 yrs and must be replaced before 5-15-2025. Corrections that have been made since the last inspection dated 5-29-18 -new drain covers have been installed -a new SVRS (Stingl RS 500) has been installed -a new flow meter have been installed appropriate to the pipe size -a new spine board has been provided -a new emergency phone has been installed THE LOCATION OF THE NEW FLOW METER WILL BE DISCUSSED AT THE TIME OF THE NEXT INSPECTION. |