[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The main drain covers were installed at an unknown date.
IF IT IS NOT KNOWN WHEN THE MAIN DRAIN COVERS WERE INSTALLED OR IF THEY HAVE BEEN IN PLACE FOR 7 YEARS OR MORE THEY MUST BE REPLACED. RETAIN THE CERTIFICATE OF COMPLIANCE, INSTALLATION INSTRUCTIONS, AND THE CERT OF INSTALLATION. Correct By: 15-May-2019
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE WEIR IN THE SKIMMER BOX. Correct By: 27-Jun-2018
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications. REDUCE THE FLOW RATE TO BELOW THE FILTER MAX OF 63 GPM Correct By: 27-Jun-2018
3701-31-04 (B)(6)(g) / Throttle valve properly installed/maintained/adjusted
Throttle valve was not properly maintained/adjusted.
Throttle valves must be maintained in the same position was when originally installed and approved. Restore the setting of the throttle valve and lock it into place. MARK THE MIN AND MAX FLOW RATE BY THE FLOW METER. (MAX 63, MIN 31) Correct By: 27-Jun-2018


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 06-June-2018