3701-31-04 (A) / Approval shall be obtained for any construction or alterations of a public swimming pool.
Public swimming pool was constructed, installed, or substantially altered without obtaining approval from the Ohio Department of Health (ODH).
Contact ODH to obtain approval for any construction/alterations before operating pool.
SUBMIT AN EQUIPMENT REPLACEMENT NOTIFICATION FORM TO THE OHIO DEPARTMENT OF HEALTH FOR THE REPLACEMENT FOR THE DISINFECTION CHEMICALS FEEDER PUMP. LMI MILTON ROY B131-470SI WAS REPLACED WITH STENNER 85M5. Correct By: 21-Jun-2021
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
THE FLOW METER INDICATOR FLOAT IS FROZEN IN PLACE. REPAIR. Correct By: 21-Jun-2021
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Gates or doors were not self-closing and lockable.
INSTALL GATES OR DOORS IN ORDER TO BE SELF-CLOSING AND SELF LATCHING AND THAT WILL NOT OPEN AUTOMATICALLY. GATE MUST BE AT LEAST 48 INCHES TALL AND THE ACTUATING DEVISE MUST BE AT LEAST 38 INCHES HIGH. OPENINGS MUST NOT BE MORE THAN 4 INCHES.
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Perimeter barrier had gaps greater than 4 inches.
Repair the perimeter barrier so that there are not any gaps greater than 4 inches anywhere along the barrier.
REPAIR FENCE BY ATTACHING THE CHAIN LINK AT THE BOTTOM OF THE FENCE POST.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 17-June-2021
Comments |
---|
TEST AND RECORD THE WATER TEMPERATURE DAILY. RECORD FINDINGS ON THE WEEKLY OLD SHEET. KEEP A COPY OF THE CERTIFICATES OF COMPLIANCE FOR THE MAIN DRAIN AT THE FACILITY. IT IS RECOMMENDED THAT A COPY OF THE CERTIFICATES BE POSTED IN THE EQUIPMENT ROOM AS A REMINDER OF WHEN THEY HAVE TO BE REPLACED AND EASE FOR THE INSPECTOR TO VERIFY INSTALLATION DATE. The operator was observed performing onsite chemical tests appropriately Our records show that the main drain suction outlet covers (Hayward WG1032 BHF) were installed 5/8/2017. The covers have a 7 year life span and must be replaced before 5/8/2024. |