[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
ACC test results were not maintained.
The test results/service records for these devices must be kept on site for review. TEST AND RECORD ACC FLOW SWITCH FUNCTION MONTHLY AND WATER TEMPERATURE DAILY. Correct By: 30-Jun-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve. INCREASE FLOW RATE TO 50 TO 63 GPM


Inspection Information


Facility Type: Spa

[?] Inspection Type: Standard

Inspection Date: 27-June-2023

Comments
Our records show that the main drain suction outlet covers (Waterway 640-472xV, Waterway 479xV) were installed 5/19/2021. The covers have a 7 year life span and must be replaced before 5/19/2028.

POST PUMP CURVE AND FLOW RATE CALCULATION.