3701-31-04 ( D )(6)(a) / ORP reading shall be 650 millivolts or greater.
ORP reading was below 650 mv
Have the ACC unit inspected to determined why the ORP is low.
ENSURE THAT THE ORP LEVEL IS 650 OR MORE. Correct By: 05-Apr-2024
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Repeat Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATION ITEM AND POSES AN IMMINENT HEALTH HAZARD. DO NOT REOPEN THE POOL UNTIL THE FREE CHLORINE LEVEL IS 1 PPM OR MORE. THE OPERATOR CLOSED THE POOL AT THE TIME OF INSPECTION. POST A SIGN AT THE DOOR STATING WARNING: POOL CLOSED.
3701-31-04 (B)(1)(g) / Water clarity shall be sufficient to see the pool bottom (or Secchi disc).
Critical Water clarity was not sufficient to see the pool bottom (or Secchi disc)
Do not operate the pool when water clarity is poor.
THIS IS A CRITICAL VIOLATION AND POSES AN IMMINENT HEALTH HAZARD. THE POOL MUST REMAIN CLOSED UNTIL THE BOTTOM OF THE POOL CAN BE CLEARLY SEEN. THE OPERATOR CLOSED THE POOL AT THE TIME OF INSPECTION. THE DOOR MUST BE POSTED WITH A SIGN STATING WARNING: POOL CLOSED AND THE DOOR LOCKED.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Repeat Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
TEST AND RECORD ALKALINITY WEEKLY. Correct By: 05-Apr-2024
3701-31-04 (B)(4)(c) / SVRS/APSOS/ACC test results/ service records are maintained
Repeat ACC test results were not maintained.
The test results for the ACC must be kept on site for review.
TEST AND RECORD THE ACC FLOW SWITCH FUNCTION MONTHLY. Correct By: 04-Apr-2024
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH AFTER ADJUSTING THE FREE CHLORINE LEVEL. Correct By: 05-Apr-2024
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 02-April-2024