3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Outlet covers were not secured. Screws missing in the drain covers.
Do not operate the pool when the outlet covers are not secured. Secure the covers prior to the pool being placed back into operation.
INSTALL DRAIN COVERS WITH ALL REQUIRED SCREWS. AT LEAST 4 SCREWS, SUPPLIED BY THE MANUFACTURER, MUST BE IN PLACE. Correct By: 08-Jun-2022
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications.
All equipment must be maintained in accordance with the manufacturers specifications.
REPAIR THE ACID FEED PUMP. OR REPLACE. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(c)(iii) / Floor areas in equipment, filter and storage rooms shall be free of standing water
There was standing water on the floor areas of the equipment room.
Remove the standing water and modify the floor so that water will flow to the drain and not be able to pool on the floor.
REPAIR LEAK CAUSING THE STANDING WATER ON THE FLOOR IN THE EQUIPMENT ROOM. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Repeat Ladders/stairs/steps were not in good repair or were not slip resistant. Tread missing on the rungs of the ladder.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
REPLACE THE TREAD ON THE STEPS ON THE LADDER. Correct By: 08-Jun-2022
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
Repeat Gates or doors were not self-closing and lockable.
Repair gates or doors in order to be self-closing and lockable.
REPAIR THE GATE SO THAT IT SELF-LATCHES.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH Correct By: 08-Jun-2022
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not provided or the unit was not tested monthly
Have the ACC unit serviced or replaced with a unit that has a flow or pressure switch with an automatic shut off valve. Provide records indicating that the unit is being tested monthly.
TEST AND RECORD THE ACC FUNCTION MONTHLY.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 06-June-2022
Comments |
---|
HAVE THE BACKFLOW PREVENTER INSPECTED ANNUALLY AND MAINTAIN DOCUMENTATION AT THE POOL. When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm Keep the chemicals’ Safety Data Sheets (SDS) in the equipment room and have Personal Protective Equipment (PPE) such as chemical gloves and goggles available for handling chemicals. The Certificate of Compliance for the main drain cover(s) is/are available in the equipment room. Our records show that the main drain suction outlet covers (Waterway 640-472xV) were installed on 7-1-21. The covers have a 7 year life span and must be replaced before 7-1-28. |