[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range. ADJUST THE pH Correct By: 20-Feb-2021
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm. ADJUST THE ALKALINITY. Correct By: 20-Feb-2021


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 19-February-2021

Comments
The pool was not open at the time of inspection.

TEST AND RECORD THE ALKALINITY WEEKLY.
USE THE TEST KIT TO TEST THE pH. DO NOT USE THE AUTOMATIC CHEMICAL CONTROL READING AS A TEST
TEST AND RECORD THE AUTOMATIC CHEMICAL CONTROL FLOW SWITCH FUNCTION MONTHLY

THE BACKFLOW PREVENTER IS DUE FOR AN INSPECTION