3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical Repeat Two screws are missing from the drain cover.
INSTALL THE TWO MISSING SCREWS IN THE DRAIN COVER.
3701-31-04 (B)(1)(b) / SVRS device(s) shall be functional.
Critical The SVRS device that is being used as a secondary means to prevent entrapment/evisceration was not functional at the time of the inspection. The SVRS alarm light was on.
Do not operate the pool when the SVRS is not functioning. Ensure the SVRS is operating properly prior to placing the pool back into operation.
RESET THE SVRS. Correct By: 01-Nov-2018
3701-31-04 (B)(4) / The licensee /authorized representative is keeping records
Repeat The licensee /authorized representative was not keeping or maintaining operational records. Tests were nt recorded daily. FC, CC, and TC were missed up. ACC and SVRS records were not monthly.
All facility records must be maintained and available for review upon request.
TEST AND RECORD FC, CC, AND TC AND TEMPERATURE DAILY. TEST AND RECORD ACC AND SRVS FUNCTION MONTHLY. Correct By: 03-Nov-2018
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST THE pH. Correct By: 03-Nov-2018
3701-31-04 (E)(2)(d) / First aid kit provided
Repeat First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
KEEP FIRST AID KIT IN POOL ROOM OR POST SIGN STATING LOCATION OF KIT.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 01-November-2018