3701-31-04 (B)(1)(e) / Automatic Chemical Controller (ACC) shall function properly.
Critical Automatic Chemical Controller (ACC) was not functioning properly at the time of the inspection. The flow switch appears not to be working again
Do not operate the pool when the ACC unit is not functioning properly. Ensure that the ACC unit is functioning properly prior to placing the pool back into operation.
REPAIR THE AUTOMATIC CHEMICAL CONTROLLER FLOW SWITCH AGAIN Correct By: 10-Aug-2019
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
REPLACE THE EMPTY ACID TANK AND DECREASE THE pH TO BETWEEN 7.8 AND 7.2 Correct By: 10-Aug-2019
Facility Type: Special Use
[?] Inspection Type: Standard
Inspection Date: 09-August-2019
Comments |
---|
The new flow meter for the waterfall pump only reads a max of 105 gpm. It appears that the flow rate for the waterfall is higher than 105 gpm. A flow meter for the range of flow should be used When using CYA (cyanuric acid) the alkalinity level is calculated by subtracting 1/3 the CYA level from the alkalinity reading. EXAMPLE: alkalinity test reading = 70 ppm, CYA = 60 ppm. Alkalinity is 70 ppm – (60/3) = 50 ppm |