[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Equipment was not maintained per manufacturers specifications. SKIMMER WEIR IS MISSING.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER. Correct By: 04-Oct-2023
3701-31-04 (B)(6)(t) / Equipment/chemical/storage areas are free of hazards/accessible only to authorized personnel.
Critical Equipment/chemical/storage areas had hazards present. CHEMICAL/TUBING IS LEAKING CHLORINE.
These storage areas must be kept free of hazards to avoid a serious public health nuisance. REPAIR THE CHLORINE LEAK FROM THE CHEMICAL PUMP / TUBING. OPERATOR WAS NOTIFIED AT THE TIME OF INSPECTION. Correct By: 27-Sep-2023
3701-31-04 (E)(2)(e) / Working emergency telephone/call box provided.
Repeat Emergency device (telephone) was not working.
Ensure that the emergency device is functioning properly and rings to the emergency response authorities. REPAIR EMERGENCY PHONE. Correct By: 04-Oct-2023


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 27-September-2023

Comments
REMEMBER TO KEEP THE CERTIFICATE OF COMPLIANCE FOR THE MAIN DRAIN COVERS AND FILL IN THE DATE OF INSTALLATION.

REPLACE THE FRAME WHEN INSTALLING THE MAIN DRAINS AND USE ALL 4 SCREWS.