3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The skimmer equalizer outlets are not covered with a VGB compliant cover.
INSTALL A VGB COMPLIANT COVER OVER THE SKIMMER EQUALIZER OUTLET OR PLUG THE OUTLET AT THE POOL WALL. Correct By: 17-Jun-2019
3701-31-04 (B)(6)(o) / Ladders/stairs/steps are in good repair/slip resistent
Ladders/stairs/steps were not in good repair or were not slip resistant.
Repair or replace the ladders/stairs/steps so that they are slip resistant and in good repair.
TIGHTEN THE HANDRAIL ON THE STEPS. Correct By: 17-Jun-2019
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST THE ALKALINITY Correct By: 17-Jun-2019
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 13-June-2019
Comments |
---|
Our records show: The main drain suction outlet cover (AquaStar 12MF) was installed 5/1/2017. The cover has a 5 year life span and must be replaced before 5/1/2022. -discard moldy or water damaged bandages in the first aid kit -additional bottom stringer is needed on the bottom of the fence (closest to the playground equipment) -it is not good practice to use a chemical bucket (5 gal) of one chemical to use as a storage tank for another chemical (muriatic acid). A supplier tank should be used. |