[?] A summary of the violations found during the inspection are listed below.

3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day.
3701-31-04 (B)(4)(a)(vi) / Total alkalinity is tested weekly
Total alkalinity was not tested weekly.
Test total alkalinity at least once/week.
3701-31-04 (B)(6) / Equipment is maintained per manufacturers specifications.
Repeat Equipment was not maintained per manufacturers specifications. One skimmer is missing a weir.
All equipment must be maintained in accordance with the manufacturers specifications. REPLACE THE MISSING WEIR IN THE SKIMMER.
3701-31-04 (B)(6)(b) / Replacement pipe is rigid PVC or the equivalent
Repeat Replacement pipe was not rigid PVC or equivalent.
Replace the non rigid PVC pipe with the proper rigid PVC pipe for public swimming pools. REPLACE THE RUBBER GASKET WITH A RIGID PVC PIPE ASTM F44/F441M-99.
3701-31-04 (B)(6)(c) / Cross connection hazards shall be prevented.
Repeat Cross connection hazards were present
Remove all cross connection hazards from the pool area. INSTALL A BACKFLOW PREVENTER ON THE HOSE BIB IN THE PUMP ROOM.
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical Flow or pressure switch for a shut off valve was not tested monthly
Provide records indicating that the unit is being tested monthly.
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.


Inspection Information


Facility Type: Pool

[?] Inspection Type: Standard

Inspection Date: 05-November-2019