3701-31-04 (B)(1)(d) / Circulation/Disinfection system shall operate properly.
Critical Disinfection system was not operating properly at the time of the inspection
Do not operate the pool when disinfection system is not operating properly. Ensure that the disinfection system is functioning properly prior to placing the pool back into operation.
REPAIR CHLORINATOR. Correct By: 02-Sep-2021
3701-31-04 (B)(4)(a)(iv) / Water temperatures are recorded daily
Water temperatures were not being recorded daily.
Take and record the water temperature at least once/day
TEST AND RECORD CHEMICAL RESULTS ON SUNDAY IF THE POOL IS OPEN. Correct By: 02-Sep-2021
RECORD FREE AND COMBINE CHLORINE CORRECTLY. TOTAL CHLORINE MAY BE GETING RECORDED AS COMBINE CHLORINE. Correct By: 02-Sep-2021 Correct By: 02-Sep-2021
3701-31-04 (B)(6)(v) / Electrical components are maintained/ free of hazards
Critical Electrical outlets had exposed wires.
Repair electrical components so the hazard is not present.
REPAIR LIGHT SWITCH AND ELECTRICAL OUTLET IN THE EQUIPMENT ROOM. Correct By: 02-Sep-2021
3701-31-04 (D)(7)(d) / Flow or pressure switch with a shut off valve shall be provided and tested monthly.
Critical ACC flow or pressure switch for a shut off valve was not provided.
Replaced the ACC flow or pressure switch.
INSTALL A FLOW SWITCH ON THE AUTOMATIC CHEMICAL CONTROLLER. Correct By: 08-Sep-2021
3701-31-04 (E)(2)(d) / First aid kit provided
First aid equipment was not provided.
Provide first aid equipment, including a first aid kit, at the pool at all times.
PROVIDE FIRST AID KIT IN POOL AREA OR POST SIGN IN POOL AREA THAT FIRST AID KIT IS AT THE FRONT DESK. Correct By: 08-Sep-2021
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 31-August-2021