3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical Chlorine disinfectant residual was less than 1 ppm for the pool
Do not operate the pool when the disinfectant residuals are less than what is required. Ensure the chlorine disinfectant residual is at 1 ppm or above prior to placing the pool back into operation.
THIS IS A CRITICAL OPERATIONAL ITEMS AND POSES AN IMMINENT HEATH HAZARD TO THE CHILDREN USING THE WADING POOL. KEEP POOL CLOSED UNTIL FREE CHLORINE LEVEL IS AT LEAST 1 PPM. OPERATOR WAS NOTIFIED TO CLOSE THE POOL. Correct By: 10-Jul-2023
3701-31-04 (B)(6)(f) / Required turnover rates are sufficient
Repeat Required turnover rates were not met.
Have the circulation system evaluated to determine why the turnover rates are not able to be met. Once the reasons have been determined have the issue repaired. If necessary, submit plans to the Ohio Department of Health to review and approve.
INCREASE FLOW RATE TO AT LEAST 50 GPM.
3701-31-04 (C)(2) / pH is within 7.2 to 7.8
pH was outside the range of 7.2 to 7.8.
Treat the pool water so that the pH is within the acceptable range.
ADJUST pH. Correct By: 12-Jul-2023
3701-31-04 (C)(3) / Total alkalinity is at or greater than 60 ppm
Repeat Total alkalinity was less than 60 ppm.
Raise the total alkalinity to at least 60 ppm.
ADJUST ALKALINITY Correct By: 12-Jul-2023
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 10-July-2023
Comments |
---|
Chemical feeder pumps should not be mounted above other chemical feeder pumps or chemical containers to prevent possible mixing of chemicals and producing toxic gas. If chlorine is mixed with muriatic acid chlorine gas is formed, which can lead to severe injuries and fatalities (SIFs) to exposed individuals. |