3701-31-04 (B)(1)(a) / Outlet covers shall be installed/secured/in compliance
Critical The equalizer lines from the skimmers were not covered with approved covers.
Screws were missing in the drain covers.
PLUG THE SKIMMER EQUALIZER LINES AT THE POOL WALL OR COVER OPENING WITH AN VGB APPROVED COVER.
INSTALL ALL 4 SCREWS IN THE DRAIN COVERS. Correct By: 11-Aug-2020
3701-31-04 (B)(1)(c) / Minimum disinfection residual shall be maintained as required.
Critical The free chlorine level is less than the 1 ppm.
This violation is a critical operational item and poses an imminent health hazard. CLOSE THE POOL UNTIL THE VIOLATION IS CORRECTED. INCREASE THE FREE CHLORINE LEVEL TO AT LEAST 1 PPM. CALL ME WHEN THE VIOLATION IS CORRECTED. 440-219-7158. Correct By: 14-Aug-2020
3701-31-04 (B)(6)(h) / Required meters and gauges maintained/functional
Required meters and gauges were not maintained or were not functional while the pool is in operation.
Maintain all meters and gauges in a properly functioning manner at all times while the pool is in operation.
REPAIR THE FLOW METER. Correct By: 11-Aug-2020
3701-31-04 (B)(6)(s) / Perimeter barrier is in good repair to prevent unauthorized entry
The gate was open at the time of inspection.
The gate did not self-close.
KEEP THE GATE CLOSED.
REPAIR THE GATE SO THAT IT SELF-CLOSES. Correct By: 11-Aug-2020
3701-31-04 (B)(6)(y) / Chemicals are properly stored/used
Critical Chemical containers were stored without labels identifying the contents.
Label and properly store all chemical containers to avoid a chemical reaction or unnecessary exposure.
KEEP BAG OF SODIUM BICARB OFF OF THE FLOOR. Correct By: 05-Aug-2020
3701-31-04 (D)(8) / Acceptable test kit provided/adequate/in good repair
Reagent R-0003 was not available for testing total chlorine (and combine chlorine)
PROVIDE REAGENT R-0003. RE-TEACH GUARD HOW TO TEST CHLORINE AND pH. Correct By: 11-Aug-2020
3701-31-04 (D)(8)(c) / Test kit reagents fresh/ properly stored.
Test kit reagents were not fresh or stored properly.
Obtain fresh reagents and store them properly.
STORE REAGENTS OUT OF THE SUN. Correct By: 05-Aug-2020
3701-31-04 (E)(3)(d) / "WARNING or DANGER - POOL CLOSED" sign(s) posted-when the pool is closed
The pool "WARNING or DANGER - POOL CLOSED" sign was not available.
PROVIDE A "WARNING or DANGER - POOL CLOSED" sign at all times the pool is not available for use. Correct By: 11-Aug-2020
Facility Type: Pool
[?] Inspection Type: Follow-up
Inspection Date: 14-August-2020