3701-31-04 (B)(4)(a)(vii) / Cyanuric acid is tested weekly
Cyanuric acid was not tested weekly.
Test for cyanuric acid level at least once/week.
3701-31-04 (B)(6)(i) / A means of determining rate-of-flow on all water pumps
A means of determining rate-of-flow was not found for all water pumps.
Properly install a flow meter or have a pump curve available for every water pump used for the pool.
3701-31-04 (C)(6) / Pool water temperature does not exceed 90 degrees Fahrenheit without approval from the Director
Pool water temperature was above 90 degrees Fahrenheit without approval from the Director of Health.
Either reduce the water temperature of the pool to below 90 degress Fahrenheit or seek approval to operate at a higher temperature from the Director of Health.
3701-31-04 (E)(2) / The public swimming pool has safety equipment visible
The safety equipment for the pool was not accessible and/or visible.
Place the safety equipment in a clearly visible area and ensure that the equipment is accessible in the event of an emergency.
Facility Type: Pool
[?] Inspection Type: Standard
Inspection Date: 10-June-2014